Modbus RTU (RS485, wired)

Eastron SDM meters, inverters with an RS485/COM port, JK BMS PB, chargers with RS485.

4 steps approx. 8 min
Create account

Step by step

  1. Requires a connector with RS485: W32 with an RS485 module or LilyGO T-Connect (module in slot 1).

  2. Connect A to A (D+), B to B (D−) and ground; use twisted pair, with a 120 Ω resistor at both ends of a long bus.

  3. In the panel, set baud rate and parity matching the device (e.g. Eastron SDM120: 2400, SDM630 and Growatt: 9600, usually 8N1) and the device's Modbus address.

  4. Each device on a single bus must have a different address.

RS485 works without Wi-Fi too — readings are queued on the connector and sent once connectivity returns.